The device provides an alarm in an addressed fire detection system and activates an acoustic and optical alarm signal in the event of a fire alarm. It is mounted on the wall e. g. along escape routes, corridors, staircases and offices. The sound level, the tones and the luminous intensity are adjustable, the devices are synchronized.
Supply and communication via FDnet/C-NET, no auxiliary power needed. The device automatically monitors its beacon and acoustic function.
The base must be ordered separately.
Supply and communication via FDnet/C-NET, no auxiliary power needed. The device automatically monitors its beacon and acoustic function.
The base must be ordered separately.
-
СвойствоЗначение
- СтандартEN 54-3, EN 54-23, EN 54-17
- Степень защитыWith base FDB226-x: IP33C With base deep FDB227-x: IP65
- Рабочее напряжениеDC 16...33 V
- Диапазон рабочих температур-25...+70 °C
- Потребляемый ток4...25 mA (tone and beacon activated)
- Количество звуковых сигналов16
- Диапазон температур хранения-30...+75 °C
- Относительная влажность?95 % rel.
- Ток в дежурном режиме400 ?A
- Уровень громкости75...99 dBA
- Интенсивность светаHigh = W-3.2-10 Medium = W-2.4-7.5 Low = O-2-6.2 Indicator
- Протокол связиFDnet/C-NET
- Сечение кабеля0.2…2.5 mm2
- Совместимость системыFDnet -> FS20 (MP7) C-NET -> FS720 (IP7)
- Размеры (? x В)116 x 42.7 мм
- Цвет~RAL 3000 flame red
- АксессуарыFDB226-R Base (wall mounting), red , FDB227-R Base deep (wall mounting), red , FDBZ293 Detector locking device , LP720 Detector locking device